Model kW stby/prime Fuel Enclosure L x W x H (in) Weight (lbs) Sound (dBA) Breaker ht (in) Door swing (ft) Tank/Runtime Fuel use (gal/hr)
D40GC 40/36 Diesel L2SA 96 x 44 x 52 2,241 67.7 19" 39 / 29 No tank
D40GC 40/36 Diesel L2SA 115 x 44 x 59 2,900 67.7 26" 39 / 29 138g int. — 33.5h / 43h / 57.5h
D50GC 50/45 Diesel L2SA 96 x 44 x 52 2,300 68.6 19" 39 / 29 No tank
D50GC 50/45 Diesel L2SA 115 x 44 x 59 3,000 68.6 26" 39 / 29 138g int. — 27.7h / 36.4h / 50.1h
D60GC 60/54 Diesel L2SA 96 x 44 x 52 2,400 69.6 19" 39 / 29 No tank
D60GC 60/54 Diesel L2SA 115 x 44 x 59 3,100 69.6 26" 39 / 29 138g int. — 24h / 27.7h / 35.6h
D80GC 80/72 Diesel L2SA 109 x 44 x 56 2,500 75.0 22" 39 / 29 No tank
D80GC 80/72 Diesel L2SA 128 x 44 x 66 3,250 75.0 32" 39 / 29 203g int. — 29h / 36.3h / 49.6h
D100GC 100/90 Diesel L2SA 109 x 44 x 56 2,650 76.4 22" 39 / 29 No tank
D100GC 100/90 Diesel L2SA 128 x 44 x 66 3,400 76.4 32" 39 / 29 203g int. — 24h / 29.7h / 40.1h
D125GC 125/114 Diesel L2SA 138 x 52 x 61.6 3,750 76.4 39 / 29 No tank
D125GC 125/114 Diesel L2SA 158 x 52 x 75.6 4,500 76.4 39 / 29 399g int. — 36h / 44.7h / 62h
D150GC 150/136 Diesel L2SA 138 x 52 x 61.6 4,050 75.4 39 / 29 No tank
D150GC 150/136 Diesel L2SA 158 x 52 x 75.6 4,850 75.4 39 / 29 399g int. — 31.5h / 38.8h / 54.2h
D175GC 175/159 Diesel L2SA 138 x 52 x 61.6 4,400 79.3 39 / 29 No tank
D175GC 175/159 Diesel L2SA 158 x 52 x 75.6 5,200 79.3 39 / 29 399g int. — 26.5h / 32.3h / 47.4h
D200GC 200/182 Diesel L2SA 138 x 52 x 61.6 4,525 79.5 39 / 29 No tank
D200GC 200/182 Diesel L2SA 158 x 52 x 75.6 5,500 79.5 39 / 29 399g int. — 24h / 29.6h / 41.6h
D250GC 250/227 Diesel L2SA 156 x 57 x 78 6,300 74.0 28" 39" No tank
D250GC 250/227 Diesel L2SA 156 x 57 x 98 7,800 74.0 48" 39" 600g int. — 28h / 35h / 47h
D250GC 250/227 Diesel L2SA 181 x 57 x 94 8,000 74.0 44" 39" 618g int Long — 28h / 35h / 47h
D300GC 300/273 Diesel L2SA 156 x 57 x 78 6,500 74.0 28" 39" No tank
D300GC 300/273 Diesel L2SA 156 x 57 x 98 8,000 74.0 48" 39" 600g int. — 24h / 31h / 40h
D300GC 300/273 Diesel L2SA 181 x 57 x 94 8,200 74.0 44" 39" 618g int Long — 24h / 31h / 40h
D350GC 350/318 Diesel L2SA 182 x 64 x 88 8,900 71.0 28" 39" No tank
D350GC 350/318 Diesel L2SA 182 x 64 x 104 10,600 71.0 44" 39" 745g int. — 27h / 31h / 42h
D350GC 350/318 Diesel L2SA 206 x 64 x 101 10,900 71.0 41" 39" 756g int. Long — 27h / 31h / 42h
D400GC 400/364 Diesel L2SA 182 x 64 x 88 8,900 71.0 28" 39" No tank
D400GC 400/364 Diesel L2SA 182 x 64 x 104 10,600 71.0 44" 39" 745g int. — 24h / 28h / 39h
D400GC 400/364 Diesel L2SA 206 x 64 x 101 10,900 71.0 41" 39" 756g int. Long — 24h / 28h / 39h
D450GC 450/409 Diesel L2SA 189 x 64 x 88 9,800 73.0 28" 39" No tank
D450GC 450/409 Diesel L2SA 182 x 64 x 104 11,800 73.0 49" 39" 970g int. — 25h / 31h / 42h
D450GC 450/409 Diesel L2SA 228 x 64 x 98 12,100 73.0 47" 39" 960g int. Long — 25h / 31h / 42h
D500GC 500/455 Diesel L2SA 189 x 64 x 88 9,900 73.0 28" 39" No tank
D500GC 500/455 Diesel L2SA 182 x 64 x 104 11,900 73.0 49" 39" 970g int. — 24h / 30h / 46h
D500GC 500/455 Diesel L2SA 228 x 64 x 98 12,100 73.0 47" 39" 960g int. Long — 24h / 30h / 46h
D550GC 550/500 Diesel L2SA 196 x 73 x 86 10,500 73.0 28" 39" No tank
D550GC 550/500 Diesel L2SA 196 x 73 x 107 13,200 73.0 47" 39" 1134g int. — 26h / 33h / 45h
D550GC 550/500 Diesel L2SA 266 x 73 x 99 13,800 73.0 39" 39" 1128g int.Long — 26h / 33h / 45h
D600GC 600/545 Diesel L2SA 196 x 73 x 86 10,700 73.0 28" 39" No tank
D600GC 600/545 Diesel L2SA 196 x 73 x 107 13,400 73.0 47" 39" 1134g int. — 24h / 30h / 42h
D600GC 600/545 Diesel L2SA 266 x 73 x 99 14,000 73.0 39" 39" 1128g int. Long — 24h / 30h / 42h

Enclosure types

Sound attenuated

Reduces radiated noise to approximately 65–75 dBA at 23 ft. Standard for commercial and institutional standby applications where noise ordinances apply.

Level 2 — Heavy-duty weatherproof

Designed for severe weather environments. Higher ingress protection than Level 1. Adds dimension and weight relative to the open genset.

Level 1 — Standard weatherproof

Suitable for most outdoor installations in moderate climates. The most common enclosure type for standby applications.

Open

No enclosure. For indoor installations or where a custom enclosure is provided by others. Dimensions reflect the naked genset only.

Tank options & runtime

Runtime figures are provided at 100%, 75%, and 50% load. Most models are available with a standard internal tank or an extended-length tank — the Long configuration adds to the overall unit footprint, which affects pad planning and clearances. Confirm tank selection before finalizing site dimensions.

For extended runtime beyond standard tank options, day tank and remote tank configurations are available on most models. Contact your application engineer.

Door swing figures reflect standard configuration. Lift-off doors are available on most models — contact your application engineer.

APPLICATION ENGINEERS

Talk to a Carter Engineer

Contact us with questions about this data, a configuration not listed here, or anything else about your project.

APPLICATION ENGINEER — DC / MD / Northern VA

Ashby Muma

Application Engineer
APPLICATION ENGINEER — VA / Southeast

Austin West

Application Engineer
Quoting & lead times

Craig Brander

Inside Sales